The data halls are built on a 900mm raised floor, with all power running under the floor and all data cabling overhead. Nandan Thakar, national infrastructure architect for ASG said he and engineers at Norman Disney Young had assessed more energy efficient options such as pods and free cooling, but Perth’s hot climate didn’t make them worth the investment.
“Our goal was to have the PUE [power usage effectiveness] as low as possible,” he said. “Before all the customer gear is migrated in, it is about 1.7. At full load, we will have the PUE down to 1.6. For a data centre of this size, located in Perth, that is about as good as it is going to get. We are not in a cool zone where we can do free air. But you still try and do as much as you can.”